Eskom warns of possible load shedding at short notice

Eskom has warned that it might have to implement Stage 2 load shedding at short notice.

In a statement, the ailing parastatal said that Stage 2 load shedding might be implemented between 16:00 - 00:00 over the next three days, following a shortage of generation capacity.

‘’The delay in returning a generation unit to service each at Arnot, Kusile and the Koeberg power stations, as well as the failure of a generation unit each at Medupi, Hendrina, Camden and two units at Majuba Power Station, have exacerbated the capacity constraints. Some generation units at other power stations are expected to return to service over the next few days.’’

‘’However, should there be any further loss of generation capacity over the next three days, or should some units fail to return to service as anticipated, loadshedding may be required to be implemented at short notice,’’ said spokesperson, Sikonathi Mantshantsha.

Eskom has urged consumers to use electricity sparingly.

‘’Eskom would like to remind the public that loadshedding is implemented only as a last resort to protect the national grid. We therefore urge all South Africans to continue using electricity sparingly especially during these uncertain times on the power system.’’

 

PICTURE: Pixabay

Done By: Mitchum George

Comments

Popular Posts